In my process of adding an EV charging station I had wanted to add 
another 20 amp 220V outlet for occasional use of other 220V equipment in 
the garage.  (band saw, radial arm saw, non business CNC machine, etc) 
With the 50 amp breaker for the charging station the sub panel is now 
full.  They make high density breakers (4 poles in the space of 2), but 
I was unable to find one for this panel.

I know the odds of one of you being specifically familiar is slim, but 
its worth a shot.

Before somebody says, "Did you try Home Depot?" in a dry nasally voice. 
Yes I tried all the usual easy suspects.

The sub panel is a GE PowerMark Gold Load Center. I am looking for a 
drop in 4 pole high density breaker in the configuration of 20/20-20/20. 
  It looks like the Siemens breakers with a UNV suffix may be a correct 
fit, but the outside poles on the only one I found were 15 amp.  All the 
existing circuits are 20 amp.  The panel is currently being used as a 
sub panel, and is full at the moment.  Other Siemens breakers I found 
that appeared to be a match will not physically fit.  They have a 
blocker plate on the connections, and the physical gap in the middle is 
to narrow.

I did also look for a GE solution since its a GE panel, but was unable 
to find anything at all.  I would ask them if they had a solution I had 
not found, but they make accepting all cookies and agreeing to receive 
SPAM a condition of contact.

The suffix UNV I found with the 15 amp poles was at Lowes. I did not 
physically try it, but visually it appears to have the correct gap to 
fit around the plastic rejection tab in the panel, the correct depth for 
the contact lugs, and correct snap in length when compared directly with 
the 50 amp GE breaker I used for the EV station.


-- 
Bob La Londe
CNC Molds N Stuff

-- 
This email has been checked for viruses by AVG antivirus software.
www.avg.com
 --- Mozilla/5.0 (Windows NT 10.0; Win64; x64; rv:102.0) Gecko/20100101
Thunderbird/102.15.1
 * Origin: A noiseless patient Spider (2:5075/128)
SEEN-BY: 5001/100 5005/49 5015/255 5019/40 5020/715
848 1042 4441 12000
SEEN-BY: 5030/49 1081 5058/104 5075/128
@PATH: 5075/128 5020/1042 4441



   GoldED+ VK   │                                                 │   09:55:30    
                                                                                
В этой области больше нет сообщений.

Остаться здесь
Перейти к списку сообщений
Перейти к списку эх